Automatic floor mounted cabinet chlorinator MR 420 C
General
- 4-20 mA proportional control input
- Modbus communication
- 5-point valve calibration
- Manual or automatic control
- LED indication of the valve position
- Vacuum indication
- High quality stepper motor
- Simple installation, set up and start up
Floor mounted cabinet chlorinator series MR 420 C is a heavy duty feed unit intended for accurate automatic or manual feed of chlorine gas. It is designed to accept a control signal from a controller (automatic control), and can simply be switched to manual control when needed.
The unit consists of:
- Motor electrical rate valve 3531 (automatic version)
- ERB gas flow meter of corresponding capacity with manual / automatic rate valve
- Vacuum switch (high/low)
- Vacuum gauge
- Wall mounting board with piping
- DP regulator (back-pressure control regulator)
The electromotive rate valve is made of compact plastic, resistant to high concentration of chlorine, with a precision rate valve and quality driving motor. The gas flowmeter is also made of compact plastic and glass, resistant to high concentration of chlorine, with a precision manual rate valve. All seals are made of materials resistant to aggressive gases (FKM, PTFE, PVDF). A differential pressure regulator is available in case of long vacuum lines or fluctuating vacuum.
Operation principle
The MR 420 C is a precise automated vacuum device: chlorine gas is not pushed but sucked through. Gas goes through the gas flow meter and the motorized rate valve, where the desired quantity is adjusted, then through the DP regulator, where vacuum fluctuations are reduced, and a check valve that prevents backflow before leaving to the ejector. The chlorinator is connected to a control unit (PLC, SCADA, WG AQUACON M 5500 C or AQUAProcessor M 5700 C) that opens or closes the motor valve according to the water flow meter and/or residual chlorine analyser. In case of controller malfunction the feed rate can be set manually on the motor valve, and in case of motor valve failure it can be adjusted by the rate valve on the gas flow meter.